This paper deals with the determination of several efficiency types of a cross-current recovery exchanger which is a part of the air venting system in the swimming pool hall on the premises of the Czech University of Life Sciences (CULS) in Prague. The product is a cross-current plate exchanger with a heat-exchanging surface of antirust aluminium. According to the manufacturer, the exchanger is fit for temperatures common in air ventilation systems. The air is forced in by fans at a flow quantity of 16,000 m3, maximum speed 2000 rpm, electric motor output 7.5 kW, filters for the air coming from the outside – grade G4, pressure loss from 42 to 200 Pa, filters for the air coming from the inside – grade G3, pressure loss from 46 to 200 Pa. The results presented are derived from in-process measurements taken on 31 January 2007 and 7 February 2007, from 9.15 to 11.30 on both days. Air temperature and air humidity were measured with 9636-51B-type sensors by Ahlborn, connected to the AHLBORN ALMEMO 5990-2 centre. These sensors were placed into each of the four input/output channels, very close to the exchanger itself (Fig. 2). The data measured were saved in the centre ...